Specifications Table for EWLQ-G-SS

EWLQ090G-SS EWLQ100G-SS EWLQ120G-SS EWLQ130G-SS EWLQ150G-SS EWLQ170G-SS EWLQ190G-SS EWLQ210G-SS EWLQ240G-SS EWLQ300G-SS EWLQ360G-SS
Sound pressure level Cooling Nom. dBA 64 67 69 70 72 72 72 74 76 76 77
Sound power level Cooling Nom. dBA 80 83 85 87 88 88 88 90 92 93 93
Refrigerant Circuits Quantity   1 1 1 1 1 1 1 1 1 1 1
  GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Dimensions Unit Width mm 928 928 928 928 928 928 928 928 928 928 928
    Depth mm 2,743 2,743 2,743 2,743 2,743 2,743 2,743 2,743 2,743 2,743 2,743
    Height mm 1,066 1,066 1,066 1,066 1,066 1,066 1,066 1,066 1,066 1,186 1,186
Compressor Type   Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor Scroll compressor
  Quantity   2 2 2 2 2 2 2 2 2 2 2
Capacity control Minimum capacity % 50.0 43.0 50.0 44.0 50.0 45.0 50.0 43.0 50.0 40.0 50.0
  Method   Step Step Step Step Step Step Step Step Step Step Step
Weight Operation weight kg 525 615 729 760 791 826 863 901 916 1,044 1,134
  Unit kg 494 578 686 714 742 773 807 838 852 967 1,046
Water heat exchanger - evaporator Type   Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger Plate heat exchanger
Cooling capacity Nom. kW 86.5 (1) 98.4 (1) 110 (1) 125 (1) 139 (1) 160 (1) 181 (1) 206 (1) 231 (1) 290 (1) 346 (1)
EER 3.86 (1) 3.81 (1) 3.78 (1) 3.79 (1) 3.79 (1) 3.80 (1) 3.86 (1) 3.80 (1) 3.85 (1) 3.84 (1) 3.77 (1)
Piping connections Discharge line connection inch 1" 5/8 1" 5/8 1" 5/8 1" 5/8 1" 5/8 1" 5/8 1" 5/8 1" 5/8 1" 5/8 2"1/8 2"1/8
Power input Cooling Nom. kW 22.4 (1) 25.8 (1) 29.2 (1) 33.0 (1) 36.8 (1) 42.0 (1) 47.0 (1) 54.2 (1) 59.9 (1) 75.6 (1) 91.8 (1)
Power supply Phase   3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~ 3~
  Frequency Hz 50 50 50 50 50 50 50 50 50 50 50
  Voltage V 400 400 400 400 400 400 400 400 400 400 400
Notes (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation. (1) - Cooling: entering evaporator water temp. 12.0°C; leaving evaporator water temp. 7.0°C; condensing temperature 45.0°C, unit at full load operation.
  (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units (2) - Sound power level (at standard conditions) is measured in accordance with ISO9614 and Eurovent 8/1 for Eurovent certified units
  (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water (3) - Fluid: Water
  (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases (4) - Its functioning relies on fluorinated greenhouse gases
  (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%. (5) - Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
  (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load (6) - Maximum starting current: starting current of biggest compressor + current of the other compressor at 75 % of maximum load
  (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current (7) - Nominal current cooling mode is referred to the following conditions: evaporator 12/7°C; condenser 30/35°C; compressors current
  (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope (8) - Maximum running current is based on max compressor absorbed current in its envelope
  (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage. (9) - Maximum unit current for wires sizing is based on minimum allowed voltage.
  (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1 (10) - Maximum current for wires sizing: compressor full load ampere x 1.1
  (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS). (11) - For more details on the operating limits please refer to the Chiller Selection Software (CSS).