Specifications Table for AZAS-MV1

AZAS71M2V1B AZAS100M7V1B AZAS125M7V1B AZAS140M7V1B
Sound pressure level Heating Nom. dBA 47 57 57 57
  Cooling Nom. dBA 46 53 53 54
Standard Accessories Tie-wraps 2 2 2 2
  Installation manual 1 1 1 1
  Refrigerant label for F-gas regulation 1 1 1 1
  General safety precautions 1 1 1 1
  LOT10 Energy Label 1 1 1 1
  Peel off F-gas label 1
Refrigerant GWP   675 675 675 675
  Charge kg 2.45 2.60 2.60 2.90
  Type   R-32 R-32 R-32 R-32
Operation range Cooling Ambient Max. °CDB 46 46 46 46
      Min. °CDB -5 -5 -5 -5
  Heating Ambient Max. °CWB 15.5 15.5 15.5 15.5
      Min. °CWB -15 -15 -15 -15
Piping connections Liquid OD mm 9.52 9.52 9.52 9.52
  Piping length OU - IU Max. m 30 30 30 30
    System Chargeless m 30 30 30 30
      Equivalent m 50 50 50 50
  Gas OD mm 15.9 15.9 15.9 15.9
  Level difference IU - IU Max. m 0.5 0.5 0.5 0.5
    IU - OU Max. m 30.0 30.0 30.0 30.0
  Additional refrigerant charge kg/m See installation manual See installation manual See installation manual See installation manual
Sound power level Cooling dBA 65 70 71 73
  Heating dBA     71 (1) 73 (1)
Dimensions Unit Width mm 900 940 940 940
    Depth mm 320 320 320 320
    Height mm 770 990 990 990
Compressor Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor
Weight Unit kg 60 70 70 78
Current - 50Hz Maximum fuse amps (MFA) A 20 25 32 32
Power supply Phase   1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240
Notes (1) - According to ENER Lot 21 (1) - According to ENER Lot 21 (1) - According to ENER Lot 21 (1) - According to ENER Lot 21
  (2) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase.
  (3) - Ssc: Short-circuit power (3) - Ssc: Short-circuit power (3) - Ssc: Short-circuit power (3) - Ssc: Short-circuit power
  (4) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current ≤ 16A per phase. (4) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current ≤ 16A per phase. (4) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current ≤ 16A per phase. (4) - European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current ≤ 16A per phase.