FXMQ200MAVE |
FXMQ250MAVE |
Sound pressure level
|
Cooling
|
At low fan speed
|
dBA
|
45
|
45
|
|
|
At high fan speed
|
dBA
|
48
|
48
|
Standard Accessories
|
Installation and operation manual
|
Installation and operation manual
|
Installation and operation manual
|
|
Connection pipes
|
Connection pipes
|
Connection pipes
|
|
Sealing pads
|
Sealing pads
|
Sealing pads
|
|
Clamps
|
Clamps
|
Clamps
|
|
Screws
|
Screws
|
Screws
|
Refrigerant
|
Type
|
|
R-410A
|
R-410A
|
Power input - 50Hz
|
Cooling
|
At high fan speed
|
kW
|
1.294
|
1.465
|
|
Heating
|
At high fan speed
|
kW
|
1.294
|
1.465
|
Cooling capacity
|
Total capacity
|
At high fan speed
|
kW
|
22.4 (1)
|
28.0 (1)
|
Piping connections
|
Liquid
|
OD
|
mm
|
9.52
|
9.52
|
|
|
Type
|
|
Flare connection
|
Flare connection
|
|
Gas
|
OD
|
mm
|
19.1
|
22.2
|
|
|
Type
|
|
Braze connection
|
Braze connection
|
|
Drain
|
|
PS1B
|
PS1B
|
Dimensions
|
Unit
|
Width
|
mm
|
1,380
|
1,380
|
|
|
Depth
|
mm
|
1,100
|
1,100
|
|
|
Height
|
mm
|
470
|
470
|
Casing
|
Material
|
|
Galvanised steel plate
|
Galvanised steel plate
|
Weight
|
Unit
|
kg
|
137
|
137
|
Fan
|
External static pressure - 50Hz
|
High
|
Pa
|
221 (4)
|
270 (4)
|
|
External static pressure - 60Hz
|
High
|
Pa
|
270
|
270
|
|
Air flow rate - 50Hz
|
Cooling
|
At high fan speed
|
m³/min
|
58
|
72
|
|
|
|
At low fan speed
|
m³/min
|
50
|
62
|
|
Air flow rate - 60Hz
|
Cooling
|
High
|
m³/min
|
58
|
72
|
|
|
|
Low
|
m³/min
|
50
|
62
|
Heating capacity
|
Total capacity
|
At high fan speed
|
kW
|
25.0 (2)
|
31.5 (2)
|
Current - 50Hz
|
Maximum fuse amps (MFA)
|
A
|
15
|
15
|
Power supply
|
Phase
|
|
1~
|
1~
|
|
Name
|
|
VE
|
VE
|
|
Frequency
|
Hz
|
50/60
|
50/60
|
|
Voltage
|
V
|
220-240/220
|
220-240/220
|
Notes
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
|
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
|
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
|
(4) - The external static pressure is changeable: change the connectors inside the electrical box, this pressure means: High static pressure - Standard
|
(4) - The external static pressure is changeable: change the connectors inside the electrical box, this pressure means: High static pressure - Standard
|
|
(5) - Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% and more.
|
(5) - Air filter is not standard accessory, but please mount it in the duct system of the suction side. Select its dust collection efficiency (gravity method) 50% and more.
|
|
(6) - Sound pressure levels are measured at 220V.
|
(6) - Sound pressure levels are measured at 220V.
|
|
(7) - Reference acoustic pressure 0 dB = 20 Pa.
|
(7) - Reference acoustic pressure 0 dB = 20 Pa.
|
|
(8) - Sound values are measured in an anechoic room.
|
(8) - Sound values are measured in an anechoic room.
|
|
(9) - Operation sound differs with operation and ambient conditions
|
(9) - Operation sound differs with operation and ambient conditions
|
|
(10) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(10) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
|
(11) - Maximum allowable voltage range variation between phases is 2%.
|
(11) - Maximum allowable voltage range variation between phases is 2%.
|
|
(12) - MCA/MFA: MCA = 1.25 x FLA
|
(12) - MCA/MFA: MCA = 1.25 x FLA
|
|
(13) - MFA ≤ 4 x FLA
|
(13) - MFA ≤ 4 x FLA
|
|
(14) - Next lower standard fuse rating minimum 15A
|
(14) - Next lower standard fuse rating minimum 15A
|
|
(15) - Select wire size based on the value of MCA
|
(15) - Select wire size based on the value of MCA
|
|
(16) - Instead of a fuse, use a circuit breaker
|
(16) - Instead of a fuse, use a circuit breaker
|