Specifications Table for FXLQ-P

FXLQ20P5VEB FXLQ25P5VEB FXLQ32P5VEB FXLQ40P2VEB FXLQ40P5VEB FXLQ50P5VEB FXLQ63P5VEB FXLQ20P2VEB (Archived) FXLQ25P2VEB (Archived) FXLQ32P2VEB (Archived) FXLQ50P2VEB (Archived) FXLQ63P2VEB (Archived)
Sound pressure level Heating At high fan speed dBA 35 35 35 38 38 39 40 35 35 35 39 40
    At low fan speed dBA 32 32 32 33 33 34 35 32 32 32 34 35
  Cooling At low fan speed dBA 32 32 32 33 33 34 35 32 32 32 34 35
    At high fan speed dBA 35 35 35 38 38 39 40 35 35 35 39 40
Refrigerant GWP   2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5 2,087.5
  Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Power input - 50Hz Cooling At high fan speed kW 0.05 (1) 0.05 (1) 0.09 (1) 0.090 (1) 0.09 (1) 0.11 (1) 0.11 (1) 0.05 (1) 0.05 (1) 0.09 (1) 0.11 (1) 0.11 (1)
  Heating At high fan speed kW 0.05 (2) 0.05 (2) 0.09 (2) 0.090 (2) 0.09 (2) 0.11 (2) 0.11 (2) 0.05 (2) 0.05 (2) 0.09 (2) 0.11 (2) 0.11 (2)
Cooling capacity Total capacity At high fan speed kW 2.2 (1) 2.8 (1) 3.6 (1) 4.5 (1) 4.5 (1) 5.6 (1) 7.1 (1) 2.2 (1) 2.8 (1) 3.6 (1) 5.6 (1) 7.1 (1)
Piping connections Liquid OD mm 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 6.35 9.52
    Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
  Gas OD mm 12.7 12.7 12.7 12.7 12.7 12.7 15.9 12.7 12.7 12.7 12.7 15.9
    Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
  Drain   O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride) O.D. 21 (Vinyl chloride)
Sound power level Cooling At high fan speed dBA 54 54 54   57 58 59 54 54 54 58 59
Air filter Type   Resin net Resin net Resin net Resin net Resin net Resin net Resin net Resin net Resin net Resin net Resin net Resin net
Dimensions Unit Width mm 1,000 1,000 1,140 1,140 1,140 1,420 1,420 1,000 1,000 1,140 1,420 1,420
    Depth mm 232 232 232 232 232 232 232 232 232 232 232 232
    Height mm 600 600 600 600 600 600 600 600 600 600 600 600
Casing Colour   Fresh white (RAL9010) / Dark grey (RAL7012) Fresh white (RAL9010) / Dark grey (RAL7012) Fresh white (RAL9010) / Dark grey (RAL7012) Fresh white (RAL9010) / Dark grey (RAL7011) Fresh white (RAL9010) / Dark grey (RAL7012) Fresh white (RAL9010) / Dark grey (RAL7012) Fresh white (RAL9010) / Dark grey (RAL7012) Fresh white (RAL9010) / Dark grey (RAL7011) Fresh white (RAL9010) / Dark grey (RAL7011) Fresh white (RAL9010) / Dark grey (RAL7011) Fresh white (RAL9010) / Dark grey (RAL7011) Fresh white (RAL9010) / Dark grey (RAL7011)
Weight Unit kg 27 27 32 32 32 38 38 27 27 32 38 38
Fan Air flow rate - 50Hz Cooling At high fan speed m³/min 7 7 8 11 11 14 16 7 7 8 14 16
      At low fan speed m³/min 6.0 6.0 6.0 8.5 8.5 11.0 12.0 6.0 6.0 6.0 11.0 12.0
  Air flow rate - 60Hz Cooling High m³/min       11
      Low m³/min       8.5
Heating capacity Total capacity At high fan speed kW 2.5 (2) 3.2 (2) 4.0 (2) 5.0 (2) 5.0 (2) 6.3 (2) 8.0 (2) 2.5 (2) 3.2 (2) 4.0 (2) 6.3 (2) 8.0 (2)
Virta - 50 Hz Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15 15 15 15 15
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~
  Name   VE VE VE VE VE VE VE VE VE VE VE VE
  Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
  (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%. (5) - Maximum allowable voltage range variation between phases is 2%.
  (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA (6) - MCA/MFA: MCA = 1.25 x FLA
  (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA (7) - MFA ≤ 4 x FLA
  (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A (8) - Next lower standard fuse rating minimum 15A
  (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA (9) - Select wire size based on the value of MCA
  (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Instead of a fuse, use a circuit breaker (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Contains fluorinated greenhouse gases (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker (10) - Instead of a fuse, use a circuit breaker
  (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Contains fluorinated greenhouse gases (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases (11) - Contains fluorinated greenhouse gases