Specifications Table for FVA-A / RZQG-L9V1

FVA100AMVEB / RZQG71L9V1B FVA71AMVEB / RZQG71L9V1B FVA100AMVEB / RZQG100L9V1B FVA140AMVEB / RZQG100L9V1B FVA125AMVEB / RZQG125L9V1B FVA140AMVEB / RZQG125L9V1B FVA140AMVEB / RZQG140L9V1B
Cooling capacity Nom. kW 6.80 6.80 9.50 9.50 12.00 12.00 13.40
Space cooling SEER   6.23 6.23 5.61 5.61 5.61 5.61 5.89
  ηs,c %             232.61
  Annual energy consumption kWh/a 383 383 593 593 749 749 1,365
  Capacity Pdesign kW 6.80 6.80 9.50 9.50 12.00 12.00 13.40
  Energy efficiency class   A++ A++ A+ A+ A+ A+
Space heating (Average climate) Capacity Pdesign kW 6.33 6.33 11.30 11.30 11.30 11.30 11.47
  SCOP/A   4.05 4.05 4.20 4.20 3.87 3.87 3.88
  Energy efficiency class   A+ A+ A+ A+ A A
  Annual energy consumption kWh/a 2,189 2,189 3,767 3,767 4,088 4,088 4,132
  ηs,h %             152.39
Nominal efficiency EER   3.37 3.37 3.81 3.81 3.21 3.21 2.79
  Annual energy consumption kWh   1,009 1,247   1,869
  COP     3.64 4.14   3.70   3.61
  Energy labeling Directive Cooling     A A   A
    Heating     A A   A
Heating capacity Nom. kW   7.50 10.80   13.50   15.50
Notes (1) - See separate drawing for operation range (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - See separate drawing for operation range (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m. (1) - See separate drawing for operation range (1) - Nominal cooling capacities are based on: indoor temperature: 27°CDB, 19°CWB, outdoor temperature: 35°CDB, equivalent refrigerant piping: 5m, level difference: 0m.
  (2) - See separate drawing for electrical data (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - See separate drawing for electrical data (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m. (2) - See separate drawing for electrical data (2) - Nominal heating capacities are based on: indoor temperature: 20°CDB, outdoor temperature: 7°CDB, 6°CWB, equivalent refrigerant piping: 5m, level difference: 0m.
    (3) - See separate drawing for operation range (3) - See separate drawing for operation range   (3) - See separate drawing for operation range   (3) - See separate drawing for operation range
    (4) - See separate drawing for electrical data (4) - See separate drawing for electrical data   (4) - See separate drawing for electrical data   (4) - See separate drawing for electrical data