Specifications Table for AHQ-C / AZQS-B(8)V1

AHQ71CV1 / AZQS71B2V1B AHQ100CV1 / AZQS100B8V1B AHQ125CV1 / AZQS125B8V1B AHQ140CV1 / AZQS140B8V1B
Cooling capacity Nom. kW 6.8 9.5 12.1 (1) 13.0 (1)
Space cooling SEER   4.65 4.60 5.14 5.77
  Annual energy consumption kWh/a 511.85 723 1,412 1,353
  Capacity Pdesign kW 6.80 9.50 12.1 13.0
  Energy efficiency class   B B
Space heating (Average climate) Capacity Pdesign kW 6.33 7.60 8.0 12.0
  SCOP/A   3.80 3.80 3.78 3.99
  Energy efficiency class   A A
  Annual energy consumption kWh/a 2,332.26 2,800 2,964 4,199
Nominal efficiency EER   3.03 2.62 2.22 (3) 2.63 (3)
  Annual energy consumption kWh 1,120 1,810
  COP   3.05 3.41
  Energy labeling Directive Cooling   B D
    Heating   D B
Heating capacity Nom. kW 7.5 10.8 13.5 (2) 15.5 (2)
Notes (1) - EER/COP according to Eurovent 2012, for use outside EU only (1) - EER/COP according to Eurovent 2012, for use outside EU only (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m
  (2) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (2) - Nominal efficiency: cooling at 35°/27° nominal load, heating at 7°/20° nominal load (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
    (3) - PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (3) - EER/COP according to Eurovent 2012, for use outside EU only (3) - EER/COP according to Eurovent 2012, for use outside EU only
    (4) - Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2
    (5) - See separate drawing for electrical data
    (6) - Contains fluorinated greenhouse gases