Specifications Table for FXFQ-PV9

FXFQ25PVE9 FXFQ32PVE9 FXFQ40PVE9 FXFQ50PVE9 FXFQ63PVE9 FXFQ80PVE9 FXFQ100PVE9 FXFQ125PVE9
Dimensions Unit Height mm 246 246 246 246 246 246 288 288
    Width mm 840 840 840 840 840 840 840 840
    Depth mm 840 840 840 840 840 840 840 840
Weight Unit kg 19.5 19.5 19.5 19.5 22 22 25 25
Casing Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate Galvanised steel plate
Refrigerant Type   R-410A R-410A R-410A R-410A R-410A R-410A R-410A R-410A
Sound pressure level Cooling Super high dBA 30.0 30.0 31.0 32.0 34.0 36.0 44.0 44.0
Piping connections Liquid Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 6.35 6.35 6.35 6.35 9.52 9.52 9.52 9.52
  Gas Type   Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection Flare connection
    OD mm 12.7 12.7 12.7 12.7 15.9 15.9 15.9 15.9
  Drain   VP25 (I.D. 25/O.D. 32) VP25 (I.D. 25/O.D. 32) VP25 (I.D. 25/O.D. 32) VP25 (I.D. 25/O.D. 32) VP25 (I.D. 25/O.D. 32) VP25 (I.D. 25/O.D. 32) VP25 (I.D. 25/O.D. 32) VP25 (I.D. 25/O.D. 32)
Decoration panel Model   BYC125K-W1 BYC125K-W1 BYC125K-W1 BYC125K-W1 BYC125K-W1 BYC125K-W1 BYC125K-W1 BYC125K-W1
  Colour   Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5) Fresh white (6.5Y 9.5/0.5)
  Dimensions Height mm 50 50 50 50 50 50 50 50
    Width mm 950 950 950 950 950 950 950 950
    Depth mm 950 950 950 950 950 950 950 950
  Weight kg 5.5 5.5 5.5 5.5 5.5 5.5 5.5 5.5
Power supply Name   VE VE VE VE VE VE VE VE
  Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60 50/60 50/60 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220 220-240/220
Current - 50Hz Maximum fuse amps (MFA) A 15 15 15 15 15 15 15 15
Notes (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal) (1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal) (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
  (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (4) - Operation sound differs with operation and ambient conditions (4) - Operation sound differs with operation and ambient conditions (4) - Operation sound differs with operation and ambient conditions (4) - Operation sound differs with operation and ambient conditions (4) - Operation sound differs with operation and ambient conditions (4) - Operation sound differs with operation and ambient conditions (4) - Operation sound differs with operation and ambient conditions (4) - Operation sound differs with operation and ambient conditions
  (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (5) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%. (6) - Maximum allowable voltage range variation between phases is 2%.
  (7) - MCA/MFA: MCA = 1.25 x FLA (7) - MCA/MFA: MCA = 1.25 x FLA (7) - MCA/MFA: MCA = 1.25 x FLA (7) - MCA/MFA: MCA = 1.25 x FLA (7) - MCA/MFA: MCA = 1.25 x FLA (7) - MCA/MFA: MCA = 1.25 x FLA (7) - MCA/MFA: MCA = 1.25 x FLA (7) - MCA/MFA: MCA = 1.25 x FLA
  (8) - MFA ≤ 4 x FLA (8) - MFA ≤ 4 x FLA (8) - MFA ≤ 4 x FLA (8) - MFA ≤ 4 x FLA (8) - MFA ≤ 4 x FLA (8) - MFA ≤ 4 x FLA (8) - MFA ≤ 4 x FLA (8) - MFA ≤ 4 x FLA
  (9) - Next lower standard fuse rating minimum 15A (9) - Next lower standard fuse rating minimum 15A (9) - Next lower standard fuse rating minimum 15A (9) - Next lower standard fuse rating minimum 15A (9) - Next lower standard fuse rating minimum 15A (9) - Next lower standard fuse rating minimum 15A (9) - Next lower standard fuse rating minimum 15A (9) - Next lower standard fuse rating minimum 15A
  (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA
  (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker