Specifications Table for FDQ-C

FDQ125C5VEB FDQ125C7VEB
Cooling capacity Total capacity Nom. kW 12.5 (1) 12.5
Heating capacity Total capacity Nom. kW 14.0 (2) 14.0
Casing Colour   Not painted (galvanised) Not painted
  Material   Galvanised steel
Dimensions Unit Height mm 300 300
    Width mm 1,400 1,400
    Depth mm 700 700
Weight Unit kg 45 45
Required ceiling void >-=-mm mm 350 350
Fan External static pressure High Pa 200 200
    Nom. Pa 50 50
Sound power level Cooling dBA 66 66
Sound pressure level Cooling High dBA 40 40
    Low dBA 33 33
  Heating High dBA 40 40
    Low dBA 33 33
Piping connections Liquid OD mm 9.52 9.52
  Gas OD mm 15.9 15.9
  Drain   VP25 (I.D. 25/O.D. 32) VP25 (I.D. 25/O.D. 32)
Drain-up height mm 625 625
Decoration panel Model   BYBS125DJW1 BYBS125DJW1
  Colour   White (10Y9/0.5) White (10Y9/0.5)
  Dimensions Height mm 55 55
    Width mm 1,500 1,500
    Depth mm 500 500
  Weight kg 6.5 6.5
Control systems Infrared remote control   BRC4C65 BRC4C65
  Wired remote control   BRC1D52, BRC1E53A, BRC1E53B, BRC1E53C BRC1D52, BRC1E53A, BRC1E53B, BRC1E53C, BRC1D528
Power input Cooling Nom. kW 0.35  
  Heating Nom. kW 0.35  
Power supply Name   VE VE
  Phase   1~ 1~
  Frequency Hz 50/60 50/60
  Voltage V 220-240/220 220-240/220
Notes (1) - Cooling: indoor temp. 27°CDB, 19.0°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m; level difference: 0m (1) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m
  (2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m; level difference: 0m (2) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
  (3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat. (3) - The sound pressure values are mentioned for a unit installed with rear suction.
  (4) - The sound pressure values are mentioned for a unit installed with rear suction. (4) - PED unit category: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC
  (5) - PED unit category: excluded from scope of PED due to article 1, item 3.6 of 97/23/EC (5) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal); level difference: 0m