جدول المواصفات لـ AZQS-B(8)V1

AZQS71B2V1B AZQS100B8V1B AZQS125B8V1B AZQS140B8V1B
الأبعاد Unit الارتفاع مم 770 990 990 1,430
    Width مم 900 940 940 940
    Depth مم 320 320 320 320
Weight Unit كغ 67 72.8 74.3 94.9
Compressor Type   Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor Hermetically sealed swing compressor
Sound power level التبريد dBA 64 70.0 71.0 70.0
  التدفئة dBA   70.0 71.0 70.0
Sound pressure level Cooling Nom. dBA 48 53 54 53
  Heating Nom. dBA 50 57 58 54
  Night quiet mode Level 1 dBA 43 49 49 49
Refrigerant Type   R-410A R-410A R-410A R-410A
  Charge كغ 2.75 2.9 2.9 4.0
  السعة TCO2Eq 5.7 6.05 6.05 8.35
  GWP   2,087.5 2,087.5 2,087.5 2,087.5
Piping connections Liquid OD مم 9.52 9.52 9.52 9.52
  Gas OD مم 15.9 15.9 15.9 15.9
  طول الأنابيب الحد الأعلى الوحدة الخارجية - الوحدة الداخلية م 50 50, 30 (1) 50, 30 (1) 50, 30 (1)
    نظام مكافئ م 70 70, 40 (1) 70, 40 (1) 70, 40 (1)
      بدون شحن م 30 30 30 30
  Additional refrigerant charge kg/m See installation manual See installation manual See installation manual See installation manual
  اختلاف المستوى IU - OU Max. م 30.0 30.0 30.0 30.0
    IU - IU Max. م   0.5 0.5 0.5
Standard Accessories أغلفة برباط 2      
  Installation manual 1      
Power supply Phase   1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240
Current - 50Hz Maximum fuse amps (MFA) آمبير   32 32 40
Notes (1) - PED: التجميع = الفئة l : مستثنى من مجال PED بسبب المقالة 1، الفقرة 3.6 من ‎97/23/EC (1) - للتركيبات مع الوحدات الداخلية FCAG~AVEB (1) - للتركيبات مع الوحدات الداخلية FCAG~AVEB (1) - للتركيبات مع الوحدات الداخلية FCAG~AVEB
  (2) - الحد الأدنى لقيمة طاقة دارة القصر الجهاز متوافق مع EN/IEC 61000-3-12: يقوم المقياس التقني الأوروبي/العالمي بتحديد قيود على إنتاج التيارات التوافقية بواسطة جهاز موصول بأجهزة الفولتية المنخفضة العامة بتيار دخل >16 آمبير و≤75 آمبير لكل طور (2) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase. (2) - EN/IEC 61000-3-12: European/international technical standard setting the limits for harmonic currents produced by equipment connected to public low-voltage system with input current larger than 16A and ≤ 75A per phase.
  (3) - RLA is based on following conditions: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB (3) - Ssc: Short-circuit power (3) - Ssc: Short-circuit power (3) - Ssc: Short-circuit power
  (4) - MFA is used to select the circuit breaker and the ground fault circuit interrupter (earth leakage circuit breaker). (4) - PED: التجميع = الفئة l : مستثنى من مجال PED بسبب المقالة 1، الفقرة 3.6 من ‎97/23/EC (4) - PED: التجميع = الفئة l : مستثنى من مجال PED بسبب المقالة 1، الفقرة 3.6 من ‎97/23/EC (4) - PED: التجميع = الفئة l : مستثنى من مجال PED بسبب المقالة 1، الفقرة 3.6 من ‎97/23/EC
  (5) - يحتوي على غازات الاحتباس الحراري المفلورة (5) - See separate drawing for electrical data (5) - See separate drawing for electrical data (5) - See separate drawing for electrical data
    (6) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A (6) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A (6) - EN/IEC 61000-3-11: European/international technical standard setting the limits for voltage changes, voltage fluctuations and flicker in public low-voltage supply systems for equipment with rated ≤ 75A