Specifications Table for FXHQ-A

FXHQ32AVEB FXHQ63AVEB FXHQ100AVEB
Power input - 50Hz Cooling Nom. kW 0.107 0.111 0.237
  Heating Nom. kW 0.107 0.111 0.237
Dimensions Unit Height mm 235 235 235
    Width mm 960 1,270 1,590
    Depth mm 690 690 690
Weight Unit kg 24 33 39
Casing Colour   Fresh White Fresh White Fresh White
  Material   Resin Resin Resin
Fan Air flow rate - 50Hz Cooling High m³/min 14.0 20.0 29.5
      Low m³/min 10.0 14.0 19.0
    Heating High m³/min 14.0 20.0 29.5
      Low m³/min 10.0 14.0 19.0
Sound pressure level Cooling High dBA 36.0 37.0 44.0
    Nom. dBA 34.0 35.0 37.0
    Low dBA 31.0 34.0 34.0
  Heating High dBA 36.0 37.0 44.0
    Nom. dBA 34.0 35.0 37.0
    Low dBA 31.0 34.0 34.0
Refrigerant Type   R-410A R-410A R-410A
  GWP   2,087.5 2,087.5 2,087.5
Sound power level Cooling High dBA 54 55 62
    Nom. dBA 52 53 55
Piping connections Liquid Type   Flare connection Flare connection Flare connection
    OD mm 6.35 9.52 9.52
  Gas Type   Flare connection Flare connection Flare connection
    OD mm 12.7 15.9 15.9
  Drain   VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26) VP20 (I.D. 20/O.D. 26)
Power supply Name   VE VE VE
  Phase   1~ 1~ 1~
  Frequency Hz 50 50 50
  Voltage V 220-240 220-240 220-240
Notes Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%. Maximum allowable voltage range variation between phases is 2%.
  MCA/MFA: MCA = 1.25 x FLA MCA/MFA: MCA = 1.25 x FLA MCA/MFA: MCA = 1.25 x FLA
  MFA ≤ 4 x FLA MFA ≤ 4 x FLA MFA ≤ 4 x FLA
  Next lower standard fuse rating minimum 16A Next lower standard fuse rating minimum 16A Next lower standard fuse rating minimum 16A
  Select wire size based on the value of MCA Select wire size based on the value of MCA Select wire size based on the value of MCA
  Instead of a fuse, use a circuit breaker Instead of a fuse, use a circuit breaker Instead of a fuse, use a circuit breaker
  Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases Contains fluorinated greenhouse gases