Specifications Table for FDYM-C

FDYM30CV1M FDYM40CV1M FDYM60CV1M FDYM71CV1M FDYM80CV1M FDYM90CV1M FDYM100CV1M FDYM125CV1M FDYM140CV1M FDYM160CV1M
Casing Colour   Without powder paint Without powder paint Without powder paint Without powder paint Without powder paint Without powder paint Without powder paint Without powder paint Without powder paint Without powder paint
  Material   Galvanised steel Galvanised steel Galvanised steel Galvanised steel Galvanised steel Galvanised steel Galvanised steel Galvanised steel Galvanised steel Galvanised steel
Dimensions Unit Height mm 261 261 261 261 285 378 305 378 378 378
    Width mm 765 905 1,065 1,200 1,007 929 1,302 1,045 1,299 1,499
    Depth mm 411 411 411 411 600 541 638 541 541 541
  Packed unit Height mm 376 376 376 376 343 415 355 415 415 415
    Width mm 951 1,091 1,251 1,386 1,138 1,126 1,461 1,245 1,497 1,701
    Depth mm 541 541 541 541 690 631 727 631 631 631
Weight Unit kg 17 21 22 25 38 39 41 42 54 62
Heat exchanger Rows Quantity   3 3 3 3 3 3 3 3 3 3
  Face area 0.115 0.143 0.176 0.203 0.240 0.277 0.340 0.310 0.400 0.470
  Fin Type   Corrugated fin Corrugated fin Corrugated fin Slit fin Corrugated fin Corrugated fin Corrugated fin Corrugated fin Corrugated fin Corrugated fin
  Tube material   Seamless copper Seamless copper Seamless copper Seamless copper Seamless copper Seamless copper Seamless copper Seamless copper Seamless copper Seamless copper
Fan Type   Centrifugal Centrifugal Centrifugal Centrifugal            
  Quantity   1 2 2 2            
  Air flow rate Cooling High m³/min 8.52 14.46 18.96 18.96 22.92 23.52 41.64 30.00 39.06 43.32
      Nom. m³/min 7.38 12.48 18.12 21.54 21.78 21.54 40.20 28.02 36.24 40.50
      Low m³/min 6.24 10.20 16.68 16.68 20.10 20.10 38.22 25.50 34.26 36.54
  External static pressure High Pa 49 49 69 41 78 167 118 176 157 157
    Nom. Pa 39 39 65 31 68 127 108 127 137 137
    Low Pa 29 20 42 18 59 88 88 93 108 98
  Air flow rate Cooling Super high m³/min         24.06 25.50 43.62 31.14 45.00 46.74
  External static pressure Super high Pa         98 206 137 206 176 176
Fan motor Quantity   1 1 1 1 1 1 1 1 1 1
  Model   Induction Induction Induction Induction Induction Induction Induction Induction Induction Induction
  Drive   Direct drive Direct drive Direct drive Direct drive Direct drive Direct drive Direct drive Direct drive Direct drive Direct drive
  Output High W 30 50 80 100 320 320 470 400 480 600
Sound power level Cooling dBA 57 (0.000) 61 (0.000) 65 (0.000) 66 (0.000) 64 (0.000) 73 (0.000) 76 (0.000) 76 (0.000) 76 (0.000) 78 (0.000)
Sound pressure level Cooling Super high dBA         44 49 55 51 53 55
    High dBA 33 37 38 40 41 46 51 49 52 53
    Nom. dBA 26 34 36 39 38 42 48 45 50 50
    Low dBA 20 29 34 36 34 38 45 41 47 47
Refrigerant Type   R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22
Air filter Type   Standard Standard Standard Standard Standard Standard Standard Standard Standard Standard
Safety devices Item 01           High pressure switch   High pressure switch High pressure switch High pressure switch
    02           Phase sequencer (3ph)   Phase sequencer (3ph) Phase sequencer Phase sequencer
    03           Discharge thermostat setting (3ph)   Discharge thermostat setting (3ph) Discharge thermostat setting Discharge thermostat setting
Item SLM wired handset SLM wired handset SLM wired handset SLM wired handset SLM wired handset SLM wired handset SLM wired handset SLM wired handset SLM wired handset SLM wired handset
Power supply Name   V1 V1 V1 V1 V1 V1 V1 V1 V1 V1
  Phase   1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50 50 50 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240 220-240 220-240 220-240 220-240 220-240 220-240
Current Nominal running current (RLA) - 50Hz Cooling A 4.0 5.7 8.3 11.7 15.1 15.0 16.5 18.0 9.0 10.0
    Heating A 3.5 4.8 8.1 11.5 13.4 14.9 16.5 16.6 6.0 8.8
Notes Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room. Sound power: test with 5ft length discharge duct, terminated flush with internal wall of reverberation room.
  Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit). Sound pressure: tested with 2m length duct at the air discharge outlet and air return inlet (1.4m below the centre of the unit).
  All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E). All units are being tested and comply to ISO5151:1994(E).