Specifications Table for FDM-JV1

FDM20JEV1K FDM25JEV1K FDM30JEV1K FDM40JEV1K FDM50JEV1K FDM60JEV1K
Power input - 50Hz Cooling Nom. kW 0.158 0.157 0.245 0.273 0.610 0.824
Casing Colour   Without powder paint Without powder paint Without powder paint Without powder paint Without powder paint Without powder paint
Dimensions Unit Height mm 261 261 292 292 378 378
    Width mm 1,065 1,200 1,228 1,228 1,299 1,499
    Depth mm 411 411 420 420 541 541
  Packed unit Height mm 376 376 392 392 415 415
    Width mm 1,251 1,386 1,396 1,396 1,497 1,701
    Depth mm 541 541 572 572 631 631
Weight Unit kg 24 26 32 32 54 62
Heat exchanger Rows Quantity   3 3 3 3 3 3
  Face area 0.16 0.19 0.28 0.28 0.41 0.48
  Fin Type   Aluminium Aluminium Aluminium Aluminium Aluminium Aluminium
  Tube diameter mm 7 7 7 7 7 7
  Tube material   Copper Copper Copper Copper Copper Copper
Fan Type   Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal Centrifugal
  Air flow rate Cooling High cfm 561 607 950 1,000 1,950 2,060
      Low cfm 522 512 750 880 1,420 1,590
  External static pressure High Pa 40 50 50 50 50 50
    Nom. Pa 38 46 50 50 50 50
    Low Pa 35 36 50 50 50 50
    Maximum available High Pa 46 64 68 60 86 80
      Medium Pa 44 59 64 56 63 65
  Air flow rate Cooling Nom. cfm 544 581 900 950 1,630 1,850
Fan motor Model   Induction Induction Induction Induction Induction Induction
  Drive   Direct drive Direct drive Direct drive Direct drive Direct drive Direct drive
  Output High W 80 90 160 180 507 700
  Index of Protection   20 20 20 20 20 20
  Insulation grade   B B B B B F
  Poles   4 4 4 4 4 4
Sound pressure level Cooling High dBA 40 41 45 46 55 58
    Nom. dBA 39 40 44 45 53 56
    Low dBA 38 38 39 44 52 54
Piping connections Drain   19.1 19.1 19.1 19.1 19.1 19.1
Air filter Type   Washable Saranet Washable Saranet Washable Saranet Washable Saranet Washable Saranet Washable Saranet
  Quantity pc 2 2 2 2 2 2
Air direction control Ducted Ducted Ducted Ducted Ducted Ducted
Control Operation   Wired Wired Wired Wired Wired Wired
Power supply Phase   1~ 1~ 1~ 1~ 1~ 1~
  Frequency Hz 50 50 50 50 50 50
  Voltage V 220-240 220-240 220-240 220-240 220-240 220-240
Current Nominal running current (RLA) - 50Hz Cooling A 0.73 0.72 1.09 1.19 2.70 3.60
Notes All units are being tested and comply to ISO 5151 (Non-ducted unit) All units are being tested and comply to ISO 5151 (Non-ducted unit) All units are being tested and comply to ISO 5151 (Non-ducted unit) All units are being tested and comply to ISO 5151 (Non-ducted unit) All units are being tested and comply to ISO 5151 (Non-ducted unit) All units are being tested and comply to ISO 5151 (Non-ducted unit)
  All specifications are subjected to change by the manufacturer without prior notice. All specifications are subjected to change by the manufacturer without prior notice. All specifications are subjected to change by the manufacturer without prior notice. All specifications are subjected to change by the manufacturer without prior notice. All specifications are subjected to change by the manufacturer without prior notice. All specifications are subjected to change by the manufacturer without prior notice.
  GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 35 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 35 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 35 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 35 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 35 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 35 DEG C OD DB (HIGH FAN)
  GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 46 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 46 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 46 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 46 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 46 DEG C OD DB (HIGH FAN) GROSS CAPACITY BASED @ 27/19 DEG C ID DB/WB & 46 DEG C OD DB (HIGH FAN)
  EER IS CALCULATED BASED ON GROSS CAPACITY EER IS CALCULATED BASED ON GROSS CAPACITY EER IS CALCULATED BASED ON GROSS CAPACITY EER IS CALCULATED BASED ON GROSS CAPACITY EER IS CALCULATED BASED ON GROSS CAPACITY EER IS CALCULATED BASED ON GROSS CAPACITY