FXAQ20PVE |
FXAQ25PVE |
FXAQ32PVE |
FXAQ40PVE |
FXAQ50PVE |
FXAQ63PVE |
Sound pressure level
|
Heating
|
At high fan speed
|
dBA
|
35.0
|
36.0
|
38.0
|
|
|
At low fan speed
|
dBA
|
31.0
|
31.0
|
31.0
|
|
Cooling
|
At low fan speed
|
dBA
|
31.0
|
31.0
|
31.0
|
|
|
At high fan speed
|
dBA
|
35.0
|
36.0
|
38.0
|
Standard Accessories
|
Installation and operation manual
|
Installation and operation manual
|
Installation and operation manual
|
Installation and operation manual
|
Installation and operation manual
|
Installation and operation manual
|
Installation and operation manual
|
|
Installation panel
|
Installation panel
|
Installation panel
|
Installation panel
|
Installation panel
|
Installation panel
|
Installation panel
|
|
Paper pattern for installation
|
Paper pattern for installation
|
Paper pattern for installation
|
Paper pattern for installation
|
Paper pattern for installation
|
Paper pattern for installation
|
Paper pattern for installation
|
|
Insulation tape
|
Insulation tape
|
Insulation tape
|
Insulation tape
|
Insulation tape
|
Insulation tape
|
Insulation tape
|
|
Clamps
|
Clamps
|
Clamps
|
Clamps
|
Clamps
|
Clamps
|
Clamps
|
|
Screws
|
Screws
|
Screws
|
Screws
|
Screws
|
Screws
|
Screws
|
Refrigerant
|
Type
|
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
R-410A
|
System
|
Connectable outdoor unit system
|
|
R410A VRV Series
|
R410A VRV Series
|
R410A VRV Series
|
Power input - 50Hz
|
Cooling
|
At high fan speed
|
kW
|
0.019 (1)
|
0.028 (1)
|
0.030 (1)
|
|
Heating
|
At high fan speed
|
kW
|
0.029 (2)
|
0.034 (2)
|
0.035 (2)
|
Cooling capacity
|
Total capacity
|
At high fan speed
|
kW
|
2.2 (1)
|
2.8 (1)
|
3.6 (1)
|
Piping connections
|
Liquid
|
OD
|
mm
|
6.35
|
6.35
|
6.35
|
6.35
|
6.35
|
9.52
|
|
|
Type
|
|
Flare connection
|
Flare connection
|
Flare connection
|
Flare connection
|
Flare connection
|
Flare connection
|
|
Gas
|
OD
|
mm
|
12.7
|
12.7
|
12.7
|
12.7
|
12.7
|
15.9
|
|
|
Type
|
|
Flare connection
|
Flare connection
|
Flare connection
|
Flare connection
|
Flare connection
|
Flare connection
|
|
Drain
|
|
VP13 (I.D. 13/O.D. 18)
|
VP13 (I.D. 13/O.D. 18)
|
VP13 (I.D. 13/O.D. 18)
|
VP13 (I.D. 13/O.D. 18)
|
VP13 (I.D. 13/O.D. 18)
|
VP13 (I.D. 13/O.D. 18)
|
Dimensions
|
Unit
|
Width
|
mm
|
795
|
795
|
795
|
1,050
|
1,050
|
1,050
|
|
|
Depth
|
mm
|
238
|
238
|
238
|
238
|
238
|
238
|
|
|
Height
|
mm
|
290
|
290
|
290
|
290
|
290
|
290
|
Casing
|
Colour
|
|
White (3.0Y8.5/0.5)
|
White (3.0Y8.5/0.5)
|
White (3.0Y8.5/0.5)
|
White (3.0Y8.5/0.5)
|
White (3.0Y8.5/0.5)
|
White (3.0Y8.5/0.5)
|
Weight
|
Unit
|
kg
|
11
|
11
|
11
|
14
|
14
|
14
|
Fan
|
Air flow rate - 50Hz
|
Cooling
|
At high fan speed
|
m³/min
|
7.5
|
8
|
8.5
|
|
|
|
At low fan speed
|
m³/min
|
4.5
|
5
|
5.5
|
|
Air flow rate - 60Hz
|
Cooling
|
High
|
m³/min
|
7.5
|
8
|
8.5
|
|
|
|
Low
|
m³/min
|
4.5
|
5
|
5.5
|
Heating capacity
|
Total capacity
|
At high fan speed
|
kW
|
2.5 (2)
|
3.2 (2)
|
4.0 (2)
|
Current - 50Hz
|
Maximum fuse amps (MFA)
|
A
|
15
|
15
|
15
|
15
|
15
|
15
|
Power supply
|
Phase
|
|
1~
|
1~
|
1~
|
1~
|
1~
|
1~
|
|
Frequency
|
Hz
|
50/60
|
50/60
|
50/60
|
50/60
|
50/60
|
50/60
|
|
Voltage
|
V
|
220-240/220
|
220-240/220
|
220-240/220
|
220-240/220
|
220-240/220
|
220-240/220
|
Notes
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
|
(1) - Cooling: indoor temp. 27°CDB, 19°CWB; outdoor temp. 35°CDB; equivalent piping length: 7.5m (horizontal)
|
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
|
(2) - Heating: indoor temp. 20°CDB; outdoor temp. 7°CDB, 6°CWB; equivalent refrigerant piping: 7.5m (horizontal)
|
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
(3) - Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
|
|
(4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
(4) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
|
|
(5) - Maximum allowable voltage range variation between phases is 2%.
|
(5) - Maximum allowable voltage range variation between phases is 2%.
|
(5) - Maximum allowable voltage range variation between phases is 2%.
|
(5) - Maximum allowable voltage range variation between phases is 2%.
|
(5) - Maximum allowable voltage range variation between phases is 2%.
|
(5) - Maximum allowable voltage range variation between phases is 2%.
|
|
(6) - MCA/MFA: MCA = 1.25 x FLA
|
(6) - MCA/MFA: MCA = 1.25 x FLA
|
(6) - MCA/MFA: MCA = 1.25 x FLA
|
(6) - MCA/MFA: MCA = 1.25 x FLA
|
(6) - MCA/MFA: MCA = 1.25 x FLA
|
(6) - MCA/MFA: MCA = 1.25 x FLA
|
|
(7) - Select wire size based on the value of MCA
|
(7) - Select wire size based on the value of MCA
|
(7) - Select wire size based on the value of MCA
|
(7) - Select wire size based on the value of MCA
|
(7) - Select wire size based on the value of MCA
|
(7) - Select wire size based on the value of MCA
|
|
(8) - Instead of a fuse, use a circuit breaker
|
(8) - Instead of a fuse, use a circuit breaker
|
(8) - Instead of a fuse, use a circuit breaker
|
(8) - Instead of a fuse, use a circuit breaker
|
(8) - Instead of a fuse, use a circuit breaker
|
(8) - Instead of a fuse, use a circuit breaker
|
|
(9) - MFA ≤ 4 x FLA
|
(9) - MFA ≤ 4 x FLA
|
(9) - MFA ≤ 4 x FLA
|
(9) - MFA ≤ 4 x FLA
|
(9) - MFA ≤ 4 x FLA
|
(9) - MFA ≤ 4 x FLA
|
Air filter
|
Type
|
|
Washable resin net
|
Washable resin net
|
Washable resin net
|