Specifications Table for VAM-FA/FB

VAM150FA8VE1 VAM250FA8VE1 VAM650FB7VE
Power input - 50Hz Heat exchange mode Nom. Ultra high kW 0.116 0.141 0.196
  Bypass mode Nom. Ultra high kW 0.116 0.141 0.196
Power input - 60Hz Heat exchange mode Nom. Ultra high kW 0.117 0.138 0.196
  Bypass mode Nom. Ultra high kW 0.117 0.138 0.196
Casing Material   Galvanised steel plate Galvanised steel plate Galvanised steel plate
Dimensions Unit الارتفاع مم 285 285 364
    Width مم 776 776 1,004
    Depth مم 525 525 868
Weight Unit كغ 24 24 52
Fan External static pressure - 50Hz Ultra high باسكال 69 64 93
  External static pressure - 60Hz Ultra high باسكال 98 98  
Operation range Relative humidity % 80% or less 80% or less 80% or less
Sound pressure level - 50Hz Heat exchange mode Ultra high dBA 27, 28.5 28, 29 34.5
  Bypass mode Ultra high dBA 27, 28.5 28, 29 34.5
Sound pressure level - 60Hz Heat exchange mode Ultra high dBA 28.5 29.5 35.5
  Bypass mode Ultra high dBA 28 29 35.5
Heat exchange system Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange Air to air cross flow total heat (sensible + latent heat) exchange
Heat exchange element Specially processed non-flammable paper Specially processed non-flammable paper Specially processed non-flammable paper
قطر مجرى التوصيل مم 100 150 200
Operation mode وضع التبادل الحراري, وضع تمرير, وضع الإنعاش وضع التبادل الحراري, وضع تمرير, وضع الإنعاش وضع التبادل الحراري, وضع تمرير, وضع الإنعاش
Item دليل التركيب والتشغيل دليل التركيب والتشغيل دليل التركيب والتشغيل
Power supply Name   VE VE VE
  Phase   1~ 1~ 1~
  Frequency Hz 50/60 50/60 50/60
  Voltage V 220-240/220 220-240/220 220-240/220
Notes (1) - Operation sound is measured at 1.5m below the center of the body. (1) - Operation sound is measured at 1.5m below the center of the body. (1) - Operation sound is measured at 1.5m below the center of the body.
  (2) - Air flow rate can be changed to Low mode or High mode. (2) - Air flow rate can be changed to Low mode or High mode. (2) - Air flow rate can be changed to Low mode or High mode.
  (3) - Normal amplitude, input and efficiency depend on the mentioned conditions. (3) - Normal amplitude, input and efficiency depend on the mentioned conditions. (3) - Normal amplitude, input and efficiency depend on the mentioned conditions.
  (4) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (4) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise. (4) - Sound values are measured in an anechoic chamber. Operating sound level generally becomes higher than this value depending on the operating conditions, reflected sound, and peripheral noise.
  (5) - The noise level at the air discharge port is about 8dB higher than the operating sound of the unit. (5) - The noise level at the air discharge port is about 8dB higher than the operating sound of the unit. (5) - The noise level at the air discharge port is about 8dB higher than the operating sound of the unit.
  (6) - The specifications, designs and information here are subject to change without notice. (6) - The specifications, designs and information here are subject to change without notice. (6) - The specifications, designs and information here are subject to change without notice.
  (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits. (7) - Voltage range: units are suitable for use on electrical systems where voltage supplied to unit terminal is not below or above listed range limits.
  (8) - Maximum allowable voltage range variation between phases is 2%. (8) - Maximum allowable voltage range variation between phases is 2%. (8) - Maximum allowable voltage range variation between phases is 2%.
  (9) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2)‎‏؛ MFA ≤ 4 x FLA‎‏؛ (يعتبر VAM2000 على أنه 2‏x‏ VAM1000) (9) - MCA/MFA: MCA = 1.25 x FLA(FM1) + FLA(FM2)‎‏؛ MFA ≤ 4 x FLA‎‏؛ (يعتبر VAM2000 على أنه 2‏x‏ VAM1000) (9) - MCA = 1.25 x FLA (FM1) + FLA (FM2)
  (10) - Select wire size based on the value of MCA (10) - Select wire size based on the value of MCA (10) - MCA represents maximum input current. MFA represents capacity which may accept MCA.
  (11) - Instead of a fuse, use a circuit breaker (11) - Instead of a fuse, use a circuit breaker (11) - Next lower standard fuse rating minimum 16A
      (12) - Select wire size based on the value of MCA
      (13) - Instead of a fuse, use a circuit breaker
      (14) - تم قياس المواصفات عند منحنى المروحة 8 (إعدادات المصنع)